EJA510E / EJA530E Pressure and Pressure Transmitter
2019-02-21 18:29 Click£ºtimes
EJA510E / EJA530E Pressure and Pressure Transmitter
A capsule B membrane box C capsule D membrane box
Measuring range -100~200kPa -0.1~2MPa -0.1~10MPa -0.1~50MPa
(-14.5~29psi) (-14.5~290psi) (-14.5~1450psi) (-14.5~7200psi)
Measuring range 10~200kPa 0.1~2MPa 0.5~10MPa 5~50MPa
(1.45~29psi) (14.5~290psi) (72.5~1450psi) (720~7200psi)
Accuracy ±0.055% ±0.055% ±0.055% ±0.055%
Protection rating IP66/IP67, NEMA 4X
Explosion-proof specifications NEPSI, FM, CENELEC ATEX, CSA, IECEx
Output signal 4~20mA DC, BRAIN, HART/HART (1~5V DC) low power consumption, FOUNDATIONTM fieldbus or PROFIBUS PA two-wire digital communication
Power supply BRAIN and HART: 10.5~42V DC (common and flameproof) 10.5~32V DC (with lightning arrester) 10.5~30V DC (intrinsically safe, n-type, non-flammable) Digital communication (BRAIN and HART: small 16.6) V DC) HART (1~5V): 9~28V DC
Fieldbus: 9~32V DC (Intrinsically Safe Entity Mode: 9~24V DC, Intrinsically Safe FISCO Mode: 9~17.5V DC)
Ambient temperature -40~85°C (-40~185°F) (normal type)
-30~80°C (-22~176°F) (built-in display)
Process temperature -40~120°C (-40~248°F) (normal type)
Large overpressure 4MPa 4MPa 20MPa 60MPa
(580psi) (580psi) (8700psi) (8700psi)
Installation Direct installation/2-inch tube installation
Wetted parts material Membrane box Hastelloy C-276
Process Connector SUS316L, Hastelloy C-276
Shell cast aluminum alloy, corrosion resistant cast aluminum alloy, ASTM CF-8M stainless steel